CODERED VTA

Exploited Brotli Decoder Flaw Spreads Into Siemens Industrial Automation Software

High
Circuit board and wiring
Photo by Towfiqu barbhuiya on Unsplash

Our team covered this Brotli decoder vulnerability in an earlier advisory when it surfaced in Linux package updates, but the picture has moved considerably since then. CISA has now published ICSA-26-321-03, in which Siemens maps CVE-2026-111497 — the out-of-bounds write dubbed Node2Shell, fixed by the Node.js project on 21 October 2026 — across sixteen of its industrial automation software products. The newly named exposure includes COMOS Walkinside, gDAP, the Project Server Web Administration Tool, SIMATIC BRAUMAT and SIMATIC SISTAR between V8.2 Update 1 and V8.2 Update 5, the SIMATIC Profiling Tool, SIMATIC WinCC OA V3.20 below 3.20.17.1 and all of V3.21, SIMATIC WinCC Runtime Professional, WinCC Companion, the WinCC Unified family including Industrial Edge, PC Runtime and SIQENCE, SIMATIC WinCC V7 and V8, TIA Administrator and the User Management Component. The flaw carries a CVSS v3 base score of 9.8 and sits in operator stations, engineering tools and identity components used across Critical Manufacturing, Food and Agriculture and Energy worldwide. Siemens has shipped fixed builds for some products and states plainly that for several others no fix is currently available.

The defect lives in the Brotli decoder source file c/dec/decode.c in Google Brotli releases 1.0.3 through 1.2.0, the same library bundled inside Node.js and, by extension, inside the web tiers of these Siemens products. A crafted Brotli-compressed stream can drive a buffer overflow that corrupts memory adjacent to the decoder state, and the consequences described range from disclosure of memory contents and a denial of service through to possible arbitrary code execution. No authentication and no user interaction are required — the attacker simply needs to get a malicious compressed stream in front of a vulnerable decoder. Siemens' own interim guidance points squarely at the HTTP path: for TIA Administrator and the User Management Component it describes an IIS request filtering rule that scans the Content-Encoding header and denies the value br, which indicates that Brotli-encoded requests reaching the web front end are the reachable route. For products with no fix, the stated holding measure is to turn Brotli compression and decompression off at the application or proxy layer where it is not strictly needed.

This is no longer a theoretical dependency problem. CVE-2026-111497 was added to the CISA Known Exploited Vulnerabilities catalogue on 27 October 2026, meaning exploitation in the wild is confirmed rather than predicted, and FIRST EPSS places the probability of exploitation activity in the next thirty days at 82.6 percent — among the highest scores assigned to any current vulnerability. The practical concern for industrial operators is where these components sit. WinCC and WinCC Unified are HMI and SCADA runtimes that sit directly in front of process control, BRAUMAT and SISTAR run batch processes in brewing and similar plants, and the User Management Component is the shared identity layer that fronts authentication for much of the Siemens software estate. A memory corruption bug that is reachable without credentials in that identity layer is an unusually attractive target, because success there offers a path into every product that trusts it. The gap between fixed and unfixed products widens the problem further: sites running SIMATIC BRAUMAT, SISTAR or WinCC OA V3.20 have a version to move to, while COMOS Walkinside, WinCC Runtime Professional, the WinCC Unified line, WinCC V7 and V8, Project Server Web Administration Tool, TIA Administrator and UMC are left on configuration-level workarounds until Siemens completes its remediation. With a confirmed exploited flaw, a very high EPSS figure and an incomplete patch set, exposure here is measured in how quickly plants can identify which of these sixteen products they actually run and whether their web interfaces accept Brotli-encoded input from untrusted networks.

Attack Surface

Web Application, Supply Chain (Third-party vendors), Infrastructure

Tactics

Initial Access, Execution, Impact

Techniques

  • T1190 – Exploit Public-Facing Application
  • T1195.001 – Compromise Software Dependencies and Development Tools
  • T1499.004 – Application or System Exploitation

SuperPRO's Threat Countermeasures Procedures

  1. Update SIMATIC BRAUMAT and SIMATIC SISTAR installations running V8.2 Update 1 through V8.2 Update 4 (8.2.0.1 to below 8.2.0.5) to V8.2 Update 5 (8.2.0.5), the fixed build named in Siemens advisory ICSA-26-321-03.
  2. Update SIMATIC WinCC OA V3.20 deployments below 3.20.17.1 to version 3.20.17.1 or later; note that WinCC OA V3.21 is listed as affected with no fixed version published yet.
  3. On TIA Administrator and the User Management Component, add the IIS request filtering rule Siemens specifies: in IIS Manager select Default Web Site, open Request Filtering then Rules, add a filtering rule named CVE-2026-111497 with Scan Headers set to Content-Encoding and Deny Strings set to br.
  4. Disable Brotli compression and decompression at the application or proxy layer for the products with no fix available – COMOS Walkinside, SIMATIC WinCC Runtime Professional, WinCC Unified for Industrial Edge, WinCC Unified PC Runtime, WinCC Unified SIQENCE, SIMATIC WinCC V7 and V8, and the Project Server Web Administration Tool – where Brotli is not strictly required.
  5. Inventory any Brotli library or binary bundled with Node.js or other software in the OT estate at versions 1.0.3 through 1.2.0 and move it to 1.0.10, 1.1.1 or 1.2.1, the releases that contain the fix for the c/dec/decode.c overflow.
  6. Restrict network reachability of the HTTP and HTTPS interfaces of WinCC, WinCC Unified, UMC and TIA Administrator to engineering VLANs or jump hosts, removing any direct exposure from enterprise or internet-facing segments until Siemens publishes fixes for the remaining products.
  7. Alert on inbound HTTP requests carrying Content-Encoding: br to Siemens WinCC, UMC, Project Server and TIA Administrator endpoints, and on unexpected crashes or restarts of the web runtime processes serving those products, as both are consistent with attempted exploitation of CVE-2026-111497.

Source

Code Red Cyber / VTA – coderedcyber.ai